Sprinkler Systems Inspection Checklist – Quick Reference Guide:
- Dry-pipe valve rooms or enclosures in unheated buildings must be checked as often as necessary when the outside temperature falls below 0 degrees Celsius to ensure the system does not freeze.
- Measures should be taken to ensure that the temperature in room or enclosure is maintained above 4 degrees Celsius. 6.5.4.9. NFC & 6.5.3.4. OFC
IMPORTANT NFPA standard maintenance procedure what should be completed before and during freezing weather (if it is not done, a small amount of water may accumulate and freeze, even a small amount of water may cause a rupture of the sprinkler system resulting in extensive damage to the sprinkler system.
- All low-point drains on dry-pipe systems should be drained as frequently as necessary to remove all moisture before freezing weather. (repeated daily until all condensation has been removed. Drum drip assemblies should be in a warm area or heated enclosure, when practical) NFPA
- Auxiliary drains must be inspected to prevent freezing. 6.5.4.8. NFC & 6.5.4.1. OFC Records Required.
- Pits containing sprinkler control valves must be kept free of water and protected against freezing. 6.5.4.3. NFC & 6.5.6.3. OFC
WEEKLY
- Valves except for electrically supervised valves, controlling water supplies to sprinklers and alarm connections must be checked to ensure that they are in the open position. 6.5.4.1. (1) NFC & 6.5.3.1. OFC
- Water supply pressure and system air pressure must be checked by using gauges to ensure system is maintained at required operating pressure. 6.5.4.7. NFC & 6.5.3.3. OFC
MONTHLY
- The alarm bell must be tested by flowing water through the test connection located at the sprinkler valve. This test must be performed on sprinkler that does not have electrical supervisory signal service (transmitters and water flow actuated devices).
- Any alarm line that is subject to freezing must be cleared of all obstructions susceptible to freezing after the test. 6.5.3.4. (2) NFC & 6.5.5.2. OFC
- Valves that are locked open must be inspected at least monthly. 6.5.4.1. NFC
2 MONTH INTERVALS
- Transmitters and water flow actuated electrical supervisory signal devices must be tested by operating the supervisory signal devices. 6.5.3.4. (2) NFC & 6.5.5.7. (1)(2) OFC. Records Required.
- Valves that are electrically supervised must be inspected at least once every 2 months. 6.5.4.1.(3) NFC Records Required.
3 MONTH INTERVALS
- The priming water for dry-pipe systems must be inspected to ensure that the proper level above the dry-pipe valve is maintained. 6.5.4.3. OFC Records Required.
6 MONTH INTERVALS
- Valve supervisory switches, tank water level devices, building and tank water temperature supervisory devices and other sprinkler system supervisory devices must be tested at least every 6 months. 6.5.3.4. (3) NFC & 6.5.5.7.(3) OFC Records Required
ANNUALLY
- Exposed sprinkler piping hangers must be checked to ensure that they are in good repair. 6.5.3.2. OFC
- Sprinkler heads must be checked at least once per year to ensure that they are free from damage, corrosion, grease, dust, paint or whitewash. Sprinkler heads that are not free from previously stated conditions are considered inoperable and must be replaced. 6.5.4.12. NFC & 6.5.3.5. OFC
- Plugs or caps of fire department connections must be removed and threads inspected for wear, rust or obstructions.
- Plugs or caps must be replaced and secured wrench tight. 6.5.4.4.(1)(2)
- If plugs or caps are missing, the fire department connections must be examined for obstructions, back flushed when conditions warrant and the plugs or caps replaced.
- Water flow alarm tests using most hydraulically remote test connection must be performed on wet sprinkler systems. 6.5.5.3. OFC Records Required.
- All mechanical and electrical alarms must be tested to ensure that they are in operative condition. 6.5.3.13. NFC
- Dry-pipe valves must be trip tested by means of system test pipe to ensure that they operate satisfactorily and sprinkler alarms are in operating condition.
- During this test the control valve is not required to be in the fully open position, however, it must be trip tested with the control valve fully open every three years. The trip time may not exceed the acceptable trip time by more than 10%. 6.5.3.12. NFC & 6.5.5.4. OFC Records Required
- Sprinkler system water supply pressure must be tested with main drain valve fully open to ensure that there are no obstructions or deterioration of main water supply. 6.5.3.11. NFC & 6.5.5.5.. OFC Records Required
- Drainage facilities are tested to ensure the drains are capable of taking the full flow from main drainpipe without causing damage. 6.5.3.11. (2) NFC
If you are a property owner or manager you are mandated to ensure that your buildings adhere to the National Fire Code. To help you with your Fire Safety and risk management planning we have put together these handy Inspection Requirements Checklists to help you avoid liability and ensure the utmost safety for all your properties.